Smoke and Heat Exhaust Ventilation System (SHEVS) Control Centre for connection of 24V- actuators
- One Smoke and Heat Exhaust group (SHE group), 3 signal lines
- max. 8A output current
- VdS approval according to VdS 2581 and VdS 2593
- Internal power supply designed and certified to DIN EN 12101-10
- Control unit designed and tested to prEN 12101-9
Types
RWZ 4-8d
max. 8A output current
Options / accessories
Option PK (RWZ 1, 2, 4, 5, RWD):
One potential-free contact (PFC) each for alarm / malfunction
Option WTM:
Outputs for controlling external warning devices in case of alarm or malfunction (e.g. multiple-tone sounder MS and strobe BL)
Option WRM: Internal Wind- and Rain Control