TM 2-M

VdS approved Fixed temperature thermal detector

  • Alarm indication by red LED
  • Easy installation with quarter-turn fastener
  • Protected against theft
  • Insensible to wind and atmospheric pressure
  • Nominal temperature 90°C
  • Response class A1R to EN 54-5:
    • Application temperature 55..80°C
    • Static reaction: 84..100°C
  • Operating voltage 9..33V-
  • Quiescent current input approx. 45μA / 24V
  • Suitable for -20..+90°C, 10..95% relative humidity
  • 100mm diameter, flat design: with base only 50 / 59mm high (standard- / relay base)
  • VdS approval no. G 200062

Accessories:

Base for detectors:

  MS 2-S:

  • Standard base for detectors series RM 2 and TM 2.
  • Dimensions: H 16mm, Ø 100mm

  MS 2-R:

  • Relay type base for detectors series RM 2 and TM 2.
  • Integrated relay with change-over contact, switching capacity 30W / 50VA,
  • max. 1A, max. 50V
  • Coil current 15mA (supply voltage 9V)
  • Operating voltage 9..33V-
  • Suitable for -20..+70°C, 10..95% relative humidity
  • E.g. for use in door closing systems. If you intend to use detector bases in combination with our SHE control centres, please contact us for details
  • Dimensions: H 25mm, Ø 100mm