VdS approved Sequence valve for pressure-dependent control of one SHEVS cylinder, with pressurising valve for supplying air to the RWA cylinder while following idle
- In normal position (pressure < 6bar) outlet CA has exhausted (SHEVS cylinder can be pulled along by a ventilation drive). When the CO2 inlet is charged with a pressure > 10bar, valve reverses, connecting the CO2 inlet to outlet CA. After system exhaust, valve will automatically reset
- Nominal switching pressure 7bar. For different switching pressures, please inquire
- Maximum operating pressure 60bar
- Ambient temperature range: -25°C to +110°C
- Nominal bore (free cross section) of valve 0,8mm, of exhaust 4mm
- VdS approval no. G 503011
- For pipe connection of the valve, 2 male connectors 1/8" (e.g. B1-6-1/8) will be required additionally
Design of the SHEVS may require reliable venting of the piping.