ZSV-BVE

VdS approved Sequence valve for pressure-dependent control of one SHEVS cylinder, with pressurising valve for supplying air to the RWA cylinder while following idle

  • In normal position (pressure < 6bar) outlet CA has exhausted (SHEVS cylinder can be pulled along by a ventilation drive). When the CO2 inlet is charged with a pressure > 10bar, valve reverses, connecting the CO2 inlet to outlet CA. After system exhaust, valve will automatically reset
  • Nominal switching pressure 7bar. For different switching pressures, please inquire
  • Maximum operating pressure 60bar
  • Ambient temperature range: -25°C to +110°C
  • Nominal bore (free cross section) of valve 0,8mm, of exhaust 4mm
  • VdS approval no. G 503011
  • For pipe connection of the valve, 2 male connectors 1/8" (e.g. B1-6-1/8) will be required additionally

Design of the SHEVS may require reliable venting of the piping.