TAVZ 2.x

VdS-Approved Combination release valve for automatic thermal release action, combined with another control method. Release of one CO2 one-way bottle with ½" UNF thread (see accessories)

  • Suitable thermo bulbs: G5-RWA-68 and G5-RWA-93 (see accessories)
  • Maximum operating pressure 80bar
  • Nominal bore (free cross section) of valve 4mm
  • Nominal bore of piercing needle 2mm
  • No destruction of thermo bulb by combination of several control methods
  • No tool required for tensioning piercing needle and thermo bulb
  • Ambient temperature range: -25°C to +110°C
  • CO2 bottle and thermo bulbs are not included in our supply
  • Drawings see data sheet TAVZ2.x
  • Design of the SHEVS may require reliable venting of the piping. 

Types:

TAVZ 2.2
Thermal/electrical release valve OPEN

  • Thermal release by thermo bulb and electrical remote release of the OPEN function by attached solenoid, 24VDC / 7W, operating mode S1 to DIN VDE 0580 (100% duty cycle). Can be tripped e.g. by the SHE impulse control IS 2 (see Electrical Parts Catalogue, controls)
  • For pipe connection of the valve, 4 male connectors 1/8" (e.g. B1-6- 1/8) will be required additionally
  • VdS approval G597018

TAVZ 2.3
Thermal/electrical release valve OPEN with ventilation

  • Thermal release by thermo bulb and electrical remote release of the OPEN function by attached solenoid, 24VDC / 7W, operating mode S1 to DIN VDE 0580 (100% duty cycle). Can be tripped e.g. by the SHE impulse control IS 2 (see Electrical Parts Catalogue, controls)
  • Integrated priority valve for venting the pipes or connecting an upstream actuation element (e.g. alarm or ventilation valve)
  • For pipe connection of the valve, 4 male connectors 1/8" (e.g. B1-6- 1/8) will be required additionally
  • VdS approval G597018

TAVZ 2.4
Thermal/pneumatical release valve OPEN

  • Thermal release by thermo bulb and pneumatical remote release of the OPEN function by attached pneumatically operated release unit, minimum release pressure 2bar, maximum operating pressure 80bar
  • Integrated priority valve for connecting an upstream actuation element (e.g. alarm or ventilation valve)
  • For pipe connection of the valve, 5 male connectors 1/8" (e.g. B1-6- 1/8) will be required additionally

TAVZ 2.5
Thermal/pneumatical release valve OPEN with ventilation

  • Thermal release by thermo bulb and pneumatical remote release ofthe OPEN function by attached pneumatically operated release unit, minimum release pressure 2bar, maximum operating pressure 80bar
  • Integrated priority valve for venting the pipes or connecting an upstream actuation element (e.g. alarm or ventilation valve)
  • For pipe connection of the valve, 5 male connectors 1/8" (e.g. B1-6-1/8) will be required additionally

Options:

F (Française): designed for CO2 bottles with W21,8 x 1/14" thread. Version for the French market
M18 x 1,5: design for CO2 bottles with M18 x 1,5 thread

For special types please inquire