- Pneumatically operated motor unlocking device for use in SHE units with ventilation function
- When SHE unit is closed and ventilation mode is on, the PMET bolt remains latched in the PMET. In ventilation mode, the SHEVS cylinder will follow idle
- When the SHE mounting is opened by the SHE cylinder, the bolt automatically disengages from the PMET unit
- When SHE mounting closes, the bolt automatically reengages with the PMET unit
- To ensure safe PMET unlocking in the case of SHE release, be sure piping of the SHEVS system is in the following order: point of CO2 release, PMET unit, SHE cylinder PMET with bolt M8
- Manual unlocking is possible and male connectors
- Minimum operating pressure 4bar
- Maximum operating pressure 60bar
- Maximum locking force 2.500N
- Ambient temperature range: -20 to +110°C
- Connection threads for screw fittings 1/8"
- VdS approval no. G 589049
Accessories:
PMET-M6: PMET bolt M6 x 40mm, including locknut
PMET-M8: PMET bolt M8 x 40mm, including locknut
PMET-M10: PMET bolt M10 x 40mm, including locknut
For special types, please inquire