Description of function
- The ETK is used to destroy a thermo bulb in the valve-series TA3 (TA3-H, TAVE3-H, TAVZ3-H).
- When the operating voltage is applied to the ETK, releases the tappet and drives its stroke of 10mm.
- After releasing the tappet can be pushed back into its initial position, whereby the internal spring get tensioned.
Mounting / technical details
- Before mounting check the scope of supply, check for transport damages and perform the commissioning.
- The ETK is screwed all the way into the designated hole in bracket of temperature valve.
- The connection of the ETK to the control is via the terminal.
- Dimensioning and connection of the lead should be performed by a qualified electric company. Take care of technical data.
- The ETK is suitable for connection to K+G / Grasl – control centres.
- When controlling by third-party control centres or other power supplies, check them for control compatibility.
Commissioning
1. Make the ETK de-energized.
2. Push the tappet all the way in.
3. The ETK is ready now. (After a releasing is the procedure to repeat)
Maintenance
- In the course of the yearly maintenance, the ETK is to inspect of visible damages, corrosion and make a check of fixture and wiring.
Disposal
- The product is made of electronic components, cables, steel, nonferrous metals and plastic. The national valid regulations regarding to these substances are observed during disposal.
Technical data
- operating voltage 24VDC (+15%/-10%)
- max. duty cycle 100% (at 20°C)
- power 3W
- push force 58N
- stroke piston 10mm
- ambient temperature -25°C to 55°C
- (2h to 95°C)
- protection class IP40
- weight 0,32kg