Description of function

  • The ETK is used to destroy a thermo bulb in the valve-series TA3 (TA3-H, TAVE3-H, TAVZ3-H).
  • When the operating voltage is applied to the ETK, releases the tappet and drives its stroke of 10mm.
  • After releasing the tappet can be pushed back into its initial position, whereby the internal spring get tensioned.

Mounting / technical details

  • Before mounting check the scope of supply, check for transport damages and perform the commissioning.
  • The ETK is screwed all the way into the designated hole in bracket of temperature valve.
  • The connection of the ETK to the control is via the terminal.
  • Dimensioning and connection of the lead should be performed by a qualified electric company. Take care of technical data.
  • The ETK is suitable for connection to K+G / Grasl – control centres.
  • When controlling by third-party control centres or other power supplies, check them for control compatibility.

Commissioning

1. Make the ETK de-energized.

2. Push the tappet all the way in.

3. The ETK is ready now. (After a releasing is the procedure to repeat)

Maintenance

  • In the course of the yearly maintenance, the ETK is to inspect of visible damages, corrosion and make a check of fixture and wiring.

Disposal

  • The product is made of electronic components, cables, steel, nonferrous metals and plastic. The national valid regulations regarding to these substances are observed during disposal.

Technical data

  • operating voltage 24VDC (+15%/-10%)
  • max. duty cycle 100% (at 20°C)
  • power 3W
  • push force 58N
  • stroke piston 10mm
  • ambient temperature -25°C to 55°C
  • (2h to 95°C)
  • protection class IP40
  • weight 0,32kg