VdS approved pressurising valve for air supply to an SHEVS cylinder following idle
- In normal condition, outlet CA has exhausted (SHEVS cylinder can be pulled along by a ventilation drive). When pressure is admitted to the CO2 inlet, the valve reverses, connecting the CO2 inlet to outlet CA. After system exhaust, the valve will automatically reset
- Maximum operating pressure 80bar
- Ambient temperature range: -25°C to +110°C
- Nominal bore (free cross section) of valve 4mm
- VdS approval no. G 598002
- For pipe connection of the valve, 2 male connectors 1/8" (e.g. B1-6- 1/8) will be required additionally
Design of the SHEVS may require reliable venting of the piping.